The settings relating to the alarm action

Model[Alarm]:
WV-SW175, WV-SW174W, WV-SW172, WV-ST165, WV-ST162
WV-SC386, WV-SW396, WV-SC385, WV-SW395, WV-SC384, WV-SW355, WV-SW352

WV-NP502*, WV-NW502S*, WV-SP306*, WV-SP305*, WV-SP302*,
WV-SF336*WV-SF335*, WV-SF332*, WV-SF346*, WV-SF342*

*Ver.1.40 or later

-The "Alarm Input" is detected when the terminal status is changed to "On"(Make). (Default)
-It is possible to configure the setting so that an alarm is detected when the terminal status is changed to "Off"(Open).

. .
Image a_point
b_point
Example
1)To change the polarity of terminal 1.
(An alarm will be detected when the terminal status is changed to "Off".)
http://IP address of the camera : + port number/cgi-bin/terminal_default?input1=nc
2)To change the polarity of terminal 1.
(An alarm will be detected when the terminal status is changed to "On".)
http://IP address of the camera : + port number/cgi-bin/terminal_default?input1=no
3)To change the polarity of terminal 2.
(An alarm will be detected when the terminal status is changed to "Off".)
http://IP address of the camera : + port number/cgi-bin/terminal_default?input2=nc
4)To change the polarity of terminal 3.
(An alarm will be detected when the terminal status is changed to "Off".)
http://IP address of the camera : + port number/cgi-bin/terminal_default?input3=nc
5)To change the polarity of terminal 1,2 and 3.
(An alarm will be detected when the terminal status is changed to "Off".)
http://IP address of the camera : + port number/cgi-bin/terminal_default?input1=nc&input2=nc&input3=nc
6)To change the polarity of terminal 1,2 and 3.
(An alarm will be detected when the terminal status is changed to "On".)(Default)
http://IP address of the camera : + port number/cgi-bin/terminal_default?input1=no&input2=no&input3=no
  • Note:
  • -*In the judgment of the short circuit detection from the opening detection, and the open detection from the short circuit detection, the minimum required detection time is 100ms at the shortest.
  • -*Since there are 5 seconds not to detect once it detects, it is the shortest 5 seconds until following detection enters.
  • -*In the judgment of "from ON to OFF" and "from OFF to ON" to I/O terminal required is 120ms in the shortest respectively.
  • -*For this reason in order to detect continuation, the shortest also needs to open the interval of 240ms or more.
  • -*Select "Alarm input" for "Terminal alarm 1/2/3" on the [Alarm] tab.